Duct transition layout: square to round duct, centred, offset or flat on one side

Updated on 28 October 2026

A duct transition joins two duct sizes, and the one laid out by hand most often is the square to round: a rectangular duct end becoming a round one. The Square to Round page lays it out in inches: set the page to inches and every result comes in fractions to the nearest 1/16 in, the thickness field takes a gauge from a list, and a free account adds the full-size template on Letter sheets and the DXF for the plasma table.

This page is the shop route: which of the three square to round pages fits the fitting on the drawing, what to measure, what the gauge changes, and what the pattern leaves for you to add. How the triangulation itself works, line by line, is in the square to round guide.

Which page for which transition

The fittingPageWhat you type
Square to round, the round centred on the rectangleSquare to RoundThe two sides X and Y, the round D, the length H and the gauge
Offset square to round: the round off centre, flat on one side or on twoEccentric Rectangle to RoundThe same, plus the offset of the round along X and along Y
Square to round with the round end tilted, not square to the ductInclined Square to RoundSquare duct only, round centred and smaller than the side: the side, the round, the height to the centre of the round and the tilt
Rectangle to rectangle: reducer, offset, plenum transitionRectangular TransitionBoth rectangles and the length; the offset ones are in the plenum guide
Round duct leaving a rectangle sideways: the register bootAngular BootSee the register boot guide

The three square to round pages build the same surface: a flat triangle on each side of the rectangle and a fan of lines at each corner, the fans carrying the curve. What changes is where the round sits. Centred, the four corners are alike, and the page develops half the fitting and mirrors it; off centre, every corner has its own true lengths, and the page walks the whole fitting round, once.

What to measure

FieldOn a duct transition
X and Y, the rectangleThe duct size at the rectangular end: 24 and 12 for a 24 × 12 trunk. On the Square to Round page the seam falls in the middle of side Y, so give Y to the side that should carry it.
D, the roundThe size of the round end: 10 for a 10 in round.
H, the lengthFrom the rectangular end to the round end, square to both: the length of the fitting along the duct, not along its sloping side.
Offsets, eccentric page onlyFrom the centre of the rectangle to the centre of the round, seen from above: one figure along X and one along Y. A negative figure moves the round the other way.
ThicknessThe gauge, from the list.

Type decimals: 10.5 for 10-1/2 in. Every size is an outside size, and the page works the pattern on the mean line, half the thickness in, so the fitting closes in the gauge you picked. On 26 gauge the outside of a 10 in round end is 0.04 in larger across than its inside, and 0.14 in larger round, about 1/8 in: enough to matter on a slip joint, so type the size the outside of each end has to be.

Offset, and flat on one side

Duct runs often need an offset transition: flat on top to run tight under the joists, flat on one side to hug a wall. On the Eccentric Rectangle to Round page that is an offset, and the offset that makes a side flat is half the difference between the duct and the round, across that side.

Flat on one side
offset = (Y − D) / 2 along Y, or (X − D) / 2 along X Along Y it flattens one of the two sides of length X; along X, one of the sides of length Y. A 24 × 12 duct, X 24 and Y 12, to a 10 in round, flat on a 24 in side: 1 in along Y and 0 along X. Flat on a 24 in side and on a 12 in side as well: 1 in along Y and 7 in along X.

The round has to stay inside the rectangle seen from above: the offset goes from zero up to that flush value and no further, and off centre the round cannot be wider than the narrow side of the duct. A 20 × 8 trunk to a 10 in round is still a normal fitting when centred, on the Square to Round page, where the flat triangles on the long sides lean out to meet the round; the eccentric page refuses it, centred or not. An offset that carries the round past the edge of the duct, to move the run over, is refused too, and no page here draws it.

Worked example: 24 × 12 to a 10 in round

A 24 × 12 in trunk (610 × 305 mm) to a 10 in round (254 mm), 12 in long (305 mm), in 26 gauge, 0.0217 in (0.55 mm).

The fittingWhat to typePlateFull-size template
CentredSquare to Round: X 24, Y 12, D 10, H 1249-1/16 × 25-1/2 in (1246 × 647 mm)21 Letter sheets
Flat on one 24 in sideEccentric Rectangle to Round: the same, with offsets X 0 and Y 1, DV 1643-11/16 × 24-1/2 in (1110 × 623 mm)18 Letter sheets
Flat on a 24 in side and a 12 in sideThe same, with offsets X 7 and Y 147-13/16 × 28-7/8 in (1214 × 733 mm)21 Letter sheets

The three are the same fitting with the round moved, so the metal hardly changes; the shape of the blank does, because the page always starts the pattern at the seam. The centred pattern is the whole fitting with its seam in the middle of a 12 in side, and an orange line runs from the middle of the opposite 12 in side to the round: cut on it and you have the two equal halves of a two-piece fitting, one seam on each 12 in side. The eccentric pattern comes in one piece.

Square to Round flat pattern: drawing of the template with the worked example dimensions
The pattern the Square to Round page draws for its own example, a 39.4 × 23.6 in rectangle (1000 × 600 mm) to a 17.7 in round (450 mm), 39.4 in long, in 3 mm plate: the cut in purple and the triangulation in orange. The orange line from the middle of the short side in the centre of the pattern splits it into two halves.

Gauge

The thickness field takes the gauge from a list. Galvanized sheet runs a little thicker than plain steel of the same number, because of the zinc:

Galvanized gaugeThicknessmm
280.0187 in0.47
260.0217 in0.55
240.0276 in0.70
220.0336 in0.85
200.0396 in1.01
180.0516 in1.31

On duct gauges the thickness moves the pattern very little: from 26 to 24 gauge, the round end of the example changes by 0.02 in round. Which gauge a duct of a given size and pressure takes comes from the job spec or SMACNA's duct construction tables, not from this page.

What the pattern does not include

  • Seam allowances. The pattern is net: the finished fitting on its mean line, with the seam edges butted. A Pittsburgh lock, a button punch snap lock, a standing seam or a lap for rivets or screws goes on along the seam edges, from the chart of your lock former: the allowance depends on the machine and the gauge, and the page does not guess it.
  • End connections. No S and drive edge, no TDC or TDF connector and no hem on the rectangular end.
  • Collars. No straight collar on either end, and no crimp or bead on the round end. A straight round collar is a plain band, on the Cylinder page; a straight run on the rectangular end is a strip folded along each side of the rectangle, added by hand.
  • Lined duct. The metal is the clear inside size plus twice the liner: type the metal size.
  • Offsets that take the round outside the rectangle, and an off-centre round wider than the narrow side of the duct.

For plasma or laser cutting, the free account exports 1 part a month in DXF; unlimited DXF export is the paid full access. Put the allowances on in your CAD before the DXF goes to the table, or along the edges of the paper template before you scribe.

Printing the template full size

  1. With a free account, enter the same figures in the full calculator and press 1:1 template on the result. In inches it comes on Letter sheets, with a cover page that maps them.
  2. Print at 100 %, actual size, portrait, with fit to page off. Measure the ruler at the foot of every sheet: it must read 4 in, or the printer scaled the page.
  3. Trim each sheet at the corner marks and lap the sheets 10 mm, about 3/8 in, matching the crosses on the shared edge; tape them by the map.
  4. Lay the paper on the sheet metal, mark the seam allowances along the seam edges, scribe round it and cut.
  5. Form the fans in small breaks along their orange lines, a little at a time, and close the seam last.

A big fitting takes a lot of paper: the centred example above takes 21 Letter sheets, and past 400 the template is refused. For a large fitting, the DXF on the table, or the layout by hand with a trammel that the square to round guide shows, is quicker.

Frequently asked questions

How do you lay out a square to round duct transition?
By triangulation: each side of the rectangle becomes a flat triangle and each corner a fan, all built from true lengths. Type the duct size, the round, the length and the gauge on the Square to Round page and it draws the pattern; with a free account it prints at full size on Letter sheets. The square to round guide works the method by hand.
What offset makes a transition flat on one side?
Half the difference between the duct and the round in the direction across that side: (Y − D) / 2 along Y flattens a side of length X. A 24 × 12 duct to a 10 in round, flat on a 24 in side, takes 1 in along Y.
Does the pattern include the Pittsburgh?
No. The pattern is net, with the seam edges butted. Add the Pittsburgh, snap lock or lap allowance along the seam edges from your lock former's chart, on the paper or in CAD before the DXF goes to the table.
Can the round be bigger than the narrow side of the duct?
Centred, yes: a 20 × 8 trunk to a 10 in round is a normal square to round. Off centre, no: the eccentric page needs the round inside the rectangle seen from above.
What gauge should a transition be?
The one the job spec or SMACNA's tables give for the duct size and pressure. The page takes the gauge you pick and works the pattern on its mean line.